English |
Español
Sankosha Y-Series Gas Tube Arresters
Applications:
Transient Voltage Surge Suppression
AC Line Protection
Power Supplies
CATV Systems
Antennas
Test Equipment
Digital Satellite Systems (DSS)
Features:
UL 1449 3rd Edition Recognized (File E328370)
Non-Radioactive
RoHS Compliant (100% Lead-Free)
Low Capacitance
Proven Performance
ISO 9001 Certified
World Renowned Quality
Part
Number
"L"
(mm)
DC Breakdown Voltage
(2)
Impulse Breakdown Voltage
Insulation Resistance
MΩ
(3)
Capac-itance
1 MHz
pF
Impulse Life 10/1000μs 500A
Impulse Discharge Current 8/20μs
AC
Discharge Current
50Hz
100V/s
100V/μs
1 Time
10 Times
(4)
9 Cycles
1 Time
1 Second
Y08Z-1000B
8.0
1,000V
≤ 1,500V
≥ 10,000
≤ 1.0pF
200 Times
10 kA
3 kA
5A
1A, 10 Times
Y-152B
8.5
1,500V
≤ 2,200V
≥ 10,000
≤ 1.0pF
10 Times
10 kA
3 kA
5A
1A, 10 Times
Y-212B
8.5
2,100V
≤ 2,700V
≥ 10,000
≤ 1.0pF
10 Times
10 kA
3 kA
5A
1A, 10 Times
Y-302B
8.5
3,000V
≤ 4,000V
≥ 10,000
≤ 1.0pF
10 Times
10 kA
1 kA
5A
1A, 10 Times
Y-402B
8.5
4,000V
≤ 5,000V
≥ 10,000
≤ 1.0pF
10 Times
10 kA
1 kA
5A
1A, 10 Times
Notes:
All part numbers are Recognized under UL 1449 3rd Edition (File E328370)
DC Breakdown Voltage Ranges are:
± 20% for Y08Z-1000B, Y-212B, Y-302B and Y-402B
± 15% for Y-152B
Insulation Resistance measured at:
DC 250V for the Y08Z-1000B
DC 500V for the Y-152B and Y-212B
DC 1,000V for the Y-302B, and 402B
5 times each polarity
Sankosha U.S.A., Inc., 406 Amapola Avenue, Suite 135, Torrance, CA 90501
Toll Free: 888.711.2436 Ph: 310.320.1661 Fax: 310.618.6869 Email:
sales@sankosha-usa.com