Applications:
Cable Telephony Products
Modems/Cable Modems
Broadband/CATV/Coaxial Protectors
xDSL Modems and Peripherals
Building Entry/Outside Plant
Transient Voltage Surge Suppression
|
Features:
UL 497B Recognized (File E140906)
High Surge Current Rating
Non-Radioactive
RoHS Compliant (100% Lead-Free)
ISO 9001 Certified
Low Capacitance ≤ 1pF
|
 |
| Part No. |
DC Breakdown Voltage (1) |
Impulse Breakdown Voltage |
Insulation Resistance MΩ(2) |
DC Holdover Voltage V(3) |
Impulse Life 10/1000μs 500A |
Impulse Discharge Current 8/20μs |
AC Discharge Current 50Hz |
| 100V/s |
100V/μs |
1kV/μs |
1 Time |
10 Times(4) |
9 Cycles 1 Time |
1 Second |
| U-1B |
75V |
≤ 500V |
≤ 700V |
≥ 10,000 |
≤ 52V |
300 Times |
10 kA |
5 kA |
65 A |
10A, 5 Times |
| U-2B |
90V |
≤ 500V |
≤ 700V |
≥ 10,000 |
≤ 52V |
300 Times |
10 kA |
5 kA |
65 A |
10A, 5 Times |
| U-3B |
145V |
≤ 500V |
≤ 700V |
≥ 10,000 |
≤ 80V |
300 Times |
10 kA |
5 kA |
65 A |
10A, 5 Times |
| U-4B |
230V |
≤ 600V |
≤ 750V |
≥ 10,000 |
≤ 135V |
300 Times |
10 kA |
5 kA |
65 A |
10A, 5 Times |
| U-5B |
250V |
≤ 600V |
≤ 800V |
≥ 10,000 |
≤ 135V |
500 Times |
10 kA |
5 kA |
65 A |
10A, 10 Times |
| U-6B |
300V |
≤ 700V |
≤ 850V |
≥ 10,000 |
≤ 150V |
500 Times |
10 kA |
5 kA |
65 A |
10A, 10 Times |
| U-7B |
350V |
≤ 700V |
≤ 850V |
≥ 10,000 |
≤ 150V |
500 Times |
10 kA |
5 kA |
65 A |
10A, 10 Times |
| U-8B |
400V |
≤ 700V |
≤ 850V |
≥ 10,000 |
≤ 150V |
500 Times |
10 kA |
5 kA |
65 A |
10A, 10 Times |
| U-9B |
470V |
≤ 700V |
≤ 850V |
≥ 10,000 |
≤ 150V |
500 Times |
10 kA |
5 kA |
65 A |
10A, 10 Times |
| U-10B |
600V |
≤ 800V |
≤ 1000V |
≥ 10,000 |
≤ 150V |
500 Times |
10 kA |
5 kA |
65 A |
10A, 10 Times |
| U-11B |
800V |
≤ 1000V |
≤ 1200V |
≥ 10,000 |
≤ 150V |
500 Times |
10 kA |
5 kA |
65 A |
10A, 10 Times |
| Notes: |
1. DC Breakdown Voltage Ranges are: |
± 20% for U-1 and U-2 |
| ± 15% for U-3, U-4, U-5, U-6, U-7, U-8, U-9, U-10 and U-11 |
|
2. Insulation Resistance measured at: |
DC 50V for the U-1, U-2 and U-3 |
| DC 100V for the U-4, U-5, U-6, U-6 and U-8 |
| DC 250V for the U-9, U-10 and U-11 |
|
3. DC Holdover Voltage measured in accordance with the ITU-T K.12 or the IEEE C62.31-1987 Test Circuit |
|
4. 5 times each polarity |
|
5. Capacitance measured at 1 MHz for all part numbers is ≤ 1.0 pF |
|
|