Sankosha Gas Discharge Tubes (GDT) - Surge Arresters




|
Applications: |
Features: |
![]() |
| Part Number |
DC Breakdown Voltage (L1-E)(L2-E)(2) |
Impulse Breakdown Voltage (L1-E)(L2-E) |
Insulation Resistance(3) | DC Holdover Voltage(4) | Impulse Life (L1+L2-E) (10/1000μs 500A) |
Impulse Discharge Current (L1+L2-E) (8/20μs) |
AC Discharge Current (L1+L2-E) (50Hz) |
|||
| 100V/s | 100V/μs | 10kV/μs | 1 Time | 10 Times(5) | 11 Cycles, 1 Time |
1 Second | ||||
| 3P-1L1 | 90V | ≤ 600V | ≤ 1050V | ≥ 10,000 MΩ | ≤ 60V | 500 Times | 20 kA | 10 kA | 180 A | 24A, 10 Times |
| 3P-4L1 | 250V | ≤ 700V | ≤ 1100V | ≥ 10,000 MΩ | ≤ 150V | 500 Times | 20 kA | 10 kA | 180 A | 24A, 10 Times |